led or incandescent emergency light exit sign Combo
|
Exit & Emergency Light Combo
Fixture
1) Injection-molded thermoplastic ABS housing.
2) Combination housing design, exit & emergency unit.
3) UL 94V-0 flame rating.
4) Innovative, snap-together design allows for fast installation.
5) Letter 6" height with 3/4" stroke.
6) Two fully adjustable compact size eyeball shape light heads for emergency light.
7) UL Number: E472028
Electrical Technology
120/277VAC dual voltage operation
Low power consumption: 2.3 watts at normal operation, 12 watts at emergency operation.
LED indicator light and push button test switch.
Light source
LEDs mounted on print circuit board (For Exit Sign); LEDs or incandescent light source for emergency.
LED lamps are operating in normal (AC input) and emergency (DC input) modes.
2 X 6V 5.4 or 6W wedge base T15 DC lamps for emergency mode.
Battery
6V 4.5Ah battery
24 hours recharge after 90 minutes discharge.
Low voltage battery disconnection-preventing deep discharge damage to the battery.
Mounting
Combination unit is suitable for surface ceiling, wall and pendant mounting.
|
|
|
|
|